Input (DC) | |
Recommended max. PV input power | 15 kWps |
Max. PV input voltage | 1100 V |
Min. PV input voltage / Start-up input voltage | 180V / 180V |
Rated input voltage | 600 V |
MPP voltage range | 160 V – 1000 V |
No. of independent MPP inputs | 2 |
No. of PV strings per MPPT | 2/1 |
Max. PV input current | 37.5 A (25 A / 12.5 A) |
Max. DC short-circuit current | 48 A (32 A / 16 A) |
Max. current for DC connector | 30 A |
Output (AC) | |
Rated AC output power | 10000 W |
Max. AC output apparent power | 11000 VA |
Rated AC output apparent power | 11000 VA |
Max. AC output current | 16.7 A |
Rated AC output current (at 230V) | 14.5 A |
Rated AC voltage | 3 / N / PE, 220 / 380 V |
3 / N / PE, 230 / 400 V | |
3 / N / PE, 240 / 415 V | |
AC voltage range | 180V – 276V / 311V - 478V |
Rated grid frequency | 50 Hz / 60 H |
Grid frequency range | 45 – 55 Hz / 55 – 65 Hz |
Harmonic (THD) | < 3 % (at rated power) |
Power factor at Rated power / Adjustable power factor | > 0.99/0.8 leading – 0.8 lagging |
Feed-in phases / Connection phases | 3 / 3-PE |
Efficiency | |
Max. efficiency | 98.50% |
European efficiency | 97.90% |
Protection&Function | |
Grid monitoring | yes |
DC reverse connection protection | yes |
AC short-circuit protection | yes |
Leakage current protection | yes |
Surge Protection | DC Type II / AC Type II |
Ground fault monitoring | yes |
DC switch | yes |
PV String current monitoring | yes |
Arc fault circuit interrupter (AFCI) | yes |
PID recovery function | yes |
General Data | |
Dimensions(W*H*D) | 370*480*195 m |
Weight | 18 kg |
Mounting method | Wall-mounting bracket |
Topology | Transformerless |
Degree of protection | IP65 |
Night power consumption | < 6 W |
Corrosion | C5 |
Operating ambient temperature range | -25 °C to 60 °C |
Allowable relative humidity range (non-condensing) | 0% – 100% |
Cooling method | Natural cooling |
Max. operating altitude | 4000 m |
Display | LED |
Communication | WLAN / Ethernet / RS485 / DI / DO |
DC connection type | MC4 (Max. 6 mm² ) |
AC connection type | Plug and play |
Grid Compliance | IEC / EN 61000-6-1/2/3/4, IEC 61000-3-2/3/11/12, IEC / EN62109-1/2, IEC 61727, IEC 62116, IEC 61683, IEC 60068-2-1/2/14/30/64/27,IEC TS 62910 , EN50530, AS/NZS 4777.2:2020, VDE-AR-N-4105, DIN VDE0126- 1-1/A1, EN50549-1, DEWA, VFR 2019, UTE C15-712-1, PSE NC RfG, UNE 206006/7 IN, MEA/PEA, G98, UNE 217002:2020, NTS V2 TypeA |
Grid Support | LVRT, HVRT,active & reactive power control and power ramp rate control |