Input (DC) | |
Max. PV input voltage | 1100 V |
Min. PV input voltage / Start-up input voltage | 200V / 250V |
Rated input voltage | 585 V |
MPP voltage range for nominal power | 550 - 850 V |
MPP voltage range | 200 V – 1000 V |
No. of independent MPP inputs | 3 |
Max. number of PV strings per MPPT | 2 |
Max. PV input current | 78 A |
Max. DC short-circuit current | 120 A |
Max. current for DC connector | 30 A |
Output (AC) | |
AC output power | 36.3 kVA @ 40 °C |
/ 33 kVA @ 45 °C | |
Max. AC output current | 55.2 A |
Rated AC voltage | 3 / N / PE, 230 / 400 V |
AC voltage range | 312 V - 528 V |
Rated grid frequency | 50 Hz / 60 Hz |
Grid frequency range | 45 – 55 Hz / 55 – 65 Hz |
Harmonic (THD) | < 3 % (at rated power) |
DC current injection | < 0.5 % In |
Power factor at Rated power / Adjustable power factor | > 0.99/0.8 leading – 0.8 lagging |
Feed-in phases / Connection phases | 3 / 3 |
Efficiency | |
Max. efficiency | 98.60% |
European efficiency | 98.30% |
Protection & Function | |
DC reverse connection protection | yes |
AC short-circuit protection | yes |
Leakage current protection | yes |
Overvoltage protection | DC Type II / AC Type II |
Grid monitoring | yes |
DC switch / AC switch | yes / no |
PV String current monitoring | yes |
Q at night | yes |
PID recovery function | optional |
General Data | |
Dimensions(W*H*D) | 702*595*310 m |
Weight | 50 kg |
Topology | Transformerless |
Degree of protection | IP66 |
Night power consumption | < 2 W |
Operating ambient temperature range | -30 °C to 60 °C (>45°C derating) |
Allowable relative humidity range (non-condensing) | 0% – 100% |
Cooling method | Smart forced air cooling |
Max. operating altitude | 4000 m (>3000m derating) |
Display | LED, Bluetooth+APP |
Communication | RS485 / Optional: Wi-Fi, Ethernet |
DC connection type | MC4 (Max. 6 mm² ) |
AC connection type | OT or DT terminal (Max.70 mm²) |
Grid Compliance | IEC 62109, IEC 61727, IEC 62116, IEC 60068, IEC 61683, VDE-AR-N 4105:2018, VDE-AR-N 4110:2018, IEC 61000-6-3, EN 50438, AS/NZS 4777.2:2015, CEI 0-21, VDE 0126-1-1/A1 VFR 2014, UTE C15-712-1:2013, DEWA |
Grid Support | Q at night function, LVRT, HVRT,active & reactive power control and power ramp rate control |